| Housing: |
Welded 20 gauge cold-rolled steel is powder coated after fabrication. Recessed housing is a shallow 3 1/2" deep by 4" wide by 13 7/8" long. Trim plate, 5 5/5" x 15 1/2", is brushed stainless steel, beveled and gasketed to smoothly meet ceiling without light leaks.
|
| Inscription: |
Letters are a full 6" high x 3/4" stroke, deep engraved around the edges, screened on a 3/16" acrylic panel. A mirror divider plate is included for double panel signs.
Inscription Options:
- Red Letters on Clear
- Green Letters on Clear
|
| Lamps: |
Red or green low wattage high intensity light emitting diodes.
Red LED emits 900mcd at 660 nanometers
Green LED emit 1000mcd at 525 nanometers
|
| Voltage: |
Operates on either 120v or 277v input.
Internal switches are set upon installation.
Low current transformer board circuit.
Red less than 57ma @ 120v, less than 26ma @ 277v.
Green less than 43ma @ 120v, less than 20ma @ 277v.
|
| Battery: |
Back-up feature uses 6v Nickel-Cadmium battery. Two hour runtime exceeds standard NFPA 90 minute requirement.
Extended run times up to 10 hours available, with alternate batteries.
|
| Finish: |
White Enamel (standard)
Black
Bronze
Brushed Stainless Steel
|
|
|
| Mounting: |
5/16" diameter knockouts are provided on top center and at each end. Four hanger bar clips are included and fit slotted sides for ceiling depth adjustment.
|
| Options: |
Recessed wall mounted with bent panel
Inverted lettering
Air plenum ceiling installation
Self-Diagnostic tester
Emergency Flash
Emergency Buzzer
Fire Alarm Interface, Flash
Fire Alarm Interface, Flash & Buzzer
|
| Codes: |
Complies with UL 924, NEC and NFPA 101 Life Safety Code. ETL Listed.
|
| Dimensions: |
| |
Panel Size |
| Height |
7 1/8" |
| Width |
13 5/8" |
|
 |
Printable Detailed Drawing
PDF Format (1.6M) |
|